Table 1: Comparison of energy consumption for groundwater cooling scheme | ||
Ìý | Groundwater cooling systems | Vapour compression refrigeration |
Cooling required | 100 kW for 1 hour | 100 kW for 1 hour |
Cooling energy output | 100 kWh | 100 kWh |
Dt for groundwater | 5 °C | N/a |
Cp for water | 4.2 kJ/kg °C | N/a |
Mass of groundwater needed | 17133 kg | N/a |
Volume of groundwater needed | 1000 m3 | N/a |
Cost of spentwater | 17.1 @ 1.135p/m3 %3D £0.19 | N/a |
COSP of cooling system | 40 | 2 |
Energy consumption kWh | 100/40%3D2.5 | 100/3 %3D 33.3 |
Energy cost@£0.082/kWh | 2.5 x 0.0082* %3D £0.205 | 33.3 x 0.082* %3D £2.73 |
Total cost | £0.395 | £2.73 |
CO2 emissions assuming 0.43 kg CO2/kWh | 1.1 kg CO2 | 14.3 kg CO2 |
*from http://www.dti.gov.uk/energy/statistics/publication/prices |
Table 2: Heating comparison for different technologies | |||
Ìý | New boiler (condensing) | Air source heat pump | Ground source heat pump |
Heating load | 100 kWh | 100 kWh | 100 kWh |
Seasonal efficiency | 88% from www.sedbuck.co.uk | 300% SPF from Hundy, 2004 | %2400% SPF from IEA, 1995 |
Energy input (kWh) | 113.6 | 33 | 25 |
Cost of energy p/kWh | 3.1 p | 8.2 p | 8.2 p |
Cost of input energy £ | £3.52 | £2.71 | £2.05 |
CO2 emitted | 21.6 kg | 14.2 kg | 10.75 kg |
Table 3: Cooling comparison for different technologies | ||
Ìý | Air source heat pump | Ground source heat pump |
Cooling load | 100 kWh | 100 kWh |
Seasonal efficiency | 280% SPF | 320 % SPF |
Energy input (kWh) | 35.7 | 31.25 |
Cost of energy p/kWh | 8.2 p | 8.2 p |
Cost of input energy £ | £2.93 | £2.56 |
CO2 emitted | 15.3 kg | 13.2 kg |