Ðǿմ«Ã½

Read our policy.

Summary of heating and cooling load comparisons at design conditions for 5 m3/s ahu
ÌýSummerWinter
ÌýCooling coilHeater batteryCooling coilHeater battery
Two-wheel ahu120 kW0012 kW
Conventional ahu171 kW42 kW0102 kW
Energy savings at design conditions51 kW42 kW090 kW