Ðǿմ«Ã½

Read our policy.

Typical all in budget rates for fire detection and alarm systems
Offices, addressable detectors in all areas (Category L1)Ìý
Shell and core installation£10-14/³¾2
Category A fit out£6-10/³¾2
Extra for void detection (where applicable)£6-10/³¾2
Hotels, addressable system with sounders in all guest bedrooms (Category L1)£12-18/³¾2
Retail supermarkets£5-7/³¾2
Retail department stores£12-18/³¾2
Leisure centres£16-22/³¾2
Residential, top quality apartments£14-18/³¾2
Residential, private dwellings (wired)£4-8/³¾2
Residential, private dwellings (radio-linked)£12-18/³¾2
Typical supply, second fix and commissioning for detectors1
Smoke detectorsÌý
IonisationÌý
Conventional£40-50/³Ü²Ô¾±³Ù
Addressable£55-70/³Ü²Ô¾±³Ù
OpticalÌý
Conventional£40-50/³Ü²Ô¾±³Ù
Addressable£55-70/³Ü²Ô¾±³Ù
Radio-linked£200-220/³Ü²Ô¾±³Ù
Duct probe£200-250/³Ü²Ô¾±³Ù
Beam detector (reflective)£400-410/³Ü²Ô¾±³Ù
Beam detector (twin set)£450-460/³Ü²Ô¾±³Ù
Aspirating very early smoke detection (Based on 10 m of pipe work)Allow £4,000
Carbon monoxide detectorsÌý
Addressable£65-80/³Ü²Ô¾±³Ù
Heat detectorsÌý
Fixed/rate of rise conventional£40-45/³Ü²Ô¾±³Ù
Addressable£45-65/³Ü²Ô¾±³Ù
Radio-linked£200-220/³Ü²Ô¾±³Ù
Flame detectorsÌý
Infrared£1,200-1,400/³Ü²Ô¾±³Ù
Ultra violet£1,500-1,800/³Ü²Ô¾±³Ù
1 Costs exclude wiringÌý
Typical supply, second fix and commissioning for alarms, control panels, interfaces etc1
Call pointsÌý
Conventional£20-30/³Ü²Ô¾±³Ù
Conventional (weatherproof)£65-85/³Ü²Ô¾±³Ù
Addressable£50-60/³Ü²Ô¾±³Ù
Addressable (weatherproof)£10-120/³Ü²Ô¾±³Ù
Radio-linked£200-220/³Ü²Ô¾±³Ù
Beacons and soundersÌý
Xenon beacon£33-38/³Ü²Ô¾±³Ù
Xenon beacon loop powered£55-60/³Ü²Ô¾±³Ù
Bell – 6 inch diameter£32-42/³Ü²Ô¾±³Ù
Bell – 8 inch diameter£40-45/³Ü²Ô¾±³Ù
Electronic sounder£35-40/³Ü²Ô¾±³Ù
Radio-linked sounder£280-310/³Ü²Ô¾±³Ù
Loop powered electronic sounder£63-68/³Ü²Ô¾±³Ù
Control panelsÌý
Conventional eight zone panel£350-400/³Ü²Ô¾±³Ù
Addressable four loop, 1000 devices (complete with batteries, led indication)£1,600-1,900/³Ü²Ô¾±³Ù
Addressable four loop, 1000 devices, network interface (complete with batteries, led indication)£2,200-2,600/³Ü²Ô¾±³Ù
Radio-linked, 96 zone panel c/w aerials£3,000-3,400/³Ü²Ô¾±³Ù
Addressable repeater panel (with batteries)£800-1100/³Ü²Ô¾±³Ù
Mimic panelÌý
Engraved perspex, A3 size£400-600/³Ü²Ô¾±³Ù
Mosaic tile, A0 size£4,500-7,000/³Ü²Ô¾±³Ù
Graphics packageÌý
PC, network interface and single node licence£1,500-1,700/³Ü²Ô¾±³Ù
Programming (based on 1000 addressable devices)£13,000-15,000
Interfaces and accessoriesÌý
Single input/output interface module£90-110/³Ü²Ô¾±³Ù
Automatic dial interface to emergency services£260-300/³Ü²Ô¾±³Ù
Magnetic door releases (24 V c/w psu) with interface£220-260/³Ü²Ô¾±³Ù
Magnetic door releases (240 V) with interface£200-220/³Ü²Ô¾±³Ù
Remote indicator£15-22/³Ü²Ô¾±³Ù
1 Costs exclude wiring
Typical circuit costs based on mics cable2
Smoke detector/heat detector (point type)£135-155/»å±ð±¹¾±³¦±ð
Call point£150-170/»å±ð±¹¾±³¦±ð
Sounder/xenon beacon£150-170/»å±ð±¹¾±³¦±ð
Loop powered sounder£135-155/»å±ð±¹¾±³¦±ð
2 Supply and first fix only