Table 1 External conditions | |||
Design area | Application | Other information | Rule of thumb |
Winter Design temperatures for heating | Without surplus boiler capacity | Ìý | -4°°ä |
Ìý | With 20% surplus boiler capacity | Single-storey building | -3°°ä |
Ìý | Ìý | Other buildings | -1°°ä |
Ìý | Rate of lowering outdoor design temperature with altitude above sea level | Ìý | -0·6°C/100 m |
Summer design temperature for air conditioning | Ìý | Dry bulb temperature | 28°°ä |
Ìý | Ìý | Wet bulb temperature | 19°°ä |
Table 2 Ventilation and air conditioning | |||
Design area | Application | Other information | Rule of thumb |
Ventilation: recommended maximum temp. | Offices | 95% operation/year | 25°°ä |
Air conditioning: recommended maximum temp | Offices | 95% operation/year | 24°°ä (or lower) |
IT rooms by classification | Type A IT rooms | Specifically designed and built for IT equipment (ideally, Isolated from office areas) | Dedicated IT room required |
Ìý | Type B IT rooms | Designed for intensive use of IT equipment at workstations (where air-conditioning must be used) | Air-conditioned office, room or workspace |
Ìý | Type C IT rooms | Room where IT equipment is used at workstations (may use natural or mechanical ventilation) | Non air-conditioned office, room or workspace |
Table 3 Room air movement | |||
Design area | Application | Other information | Rule of thumb |
Maximum recommended mean air velocities | Ìý | In winter | 0·15 m/s |
Ìý | Ìý | In summer | 0·25 m/s |
Ìý | Ìý | At 21°C | 0·15 m/s |
Ìý | Ìý | At 22°°ä | 0·20 m/s |
Ìý | Ìý | At 23°C | 0·25 m/s |
Ìý | Ìý | At 24°°ä | 0·30 m/s |
Ìý | Ìý | On back of neck | 0·20 m/s |
Ìý | Ìý | Papers will lift at velocities in excess of | 0·80 m/s |
Ìý | Ìý | Television and broadcasting studios | 0·20-0·30 m/s |
Table 4 Noise levels | |||
Design area | Application | Other information | Rule of thumb |
Recommended maximum background noise levels | Very quiet rooms | Concert halls, sound studios | NR 20 |
Ìý | Quiet rooms | Bedrooms, theatres, churches | NR 25 |
Ìý | Private rooms | Small offices, libraries, living rooms | NR 30 |
Ìý | Public rooms | General offices, classrooms, small shops | NR 35 |
Ìý | General areas | Reception areas, restaurants | NR 40 |
Ìý | Work areas | Kitchens, computer rooms, large shops | NR 45 |
Ìý | Industrial areas | Factories | NR 50 or above |
Intelligibility of telephone conversation background noise levels | Ìý | Satisfactory | Up to NR 50 |
Ìý | Ìý | Slightly difficult | Up to NR 60 |
Ìý | Ìý | Difficult | Up to NR 60 |
Ìý | Ìý | Unsatisfactory | Over NR 75 |
External noise level criteria for new noise (above background noise) | Ìý | If more than 10 dBA | Complaints expected |
Ìý | Ìý | If less than 5 dBA | Marginal |
Limiting distances for speech intelligibility (background noise level) | Ìý | Up to NR 40 | 7·0 m |
Ìý | Ìý | Up to NR 45 | 4·0 m |
Ìý | Ìý | Up to NR 50 | 2·2 m |
Ìý | Ìý | Up to NR 55 | 1·2 m |
Ìý | Ìý | Over NR 70 | Too noisy |
Table 5: Comfort data sheet | ||||||
Ðǿմ«Ã½ type | Internal design temperature | Infiltration | Ventilation | Lighting level | Noise level | Ìý |
Ìý | Summer | Winter | (ac/h) | fresh air | (Lux) | (NR) |
Cinemas (sedentary role) | 21-23°°ä | 19-21°°ä | 0·5 ac/h | 8 l/s/person | 300 lux | NR25 - NR30 |
Computer rooms (general) | 21-23°°ä | 19-21°°ä | 1 ac/h | 8 l/s/person | 300 lux | NR35 - NR45 |
Education (teaching spaces) | 21-23°°ä | 19-21°°ä | 2 ac/h | 8 l/s/person | 300 lux | NR25 - NR35 |
Exhibition hall/conference facilities | 21-23°°ä | 19-21°°ä | 0.25-0.5 ac/h | 8 l/s/person | 300 lux | NR40 |
Factory/warehouse | 21-23°°ä | 11-21°°ä | 0.25-2.5 ac/h | 8 l/s/person | 750-1000 lux | NR45 - NR 65 |
Fitness/health clubs (equipment rooms) | 18°°ä | 12-18°°ä | 0.75 ac/h | 10-12 ac/h | 300 lux | NR30 - NR40 |
Hospitals (ward and patient areas) | 23-25°°ä | 22-24°°ä | 2 ac/h | 8 l/s/person | 50 - 100 lux | NR30 – NR35 |
Hotels (bedrooms) | 21-23°°ä | 19-21°°ä | 1 ac/h | 8 l/s/person | 50 - 100 lux | NR20 – NR30 |
Libraries (reading rooms) | 24-25°°ä | 22-23°°ä | 0·25-0·75 ac/h | 8 l/s/person | 300 lux | NR30 – NR35 |
Museums and galleries (display, storage) | 21-23°°ä | 19-21°°ä | 1 ac/h | 8 l/s/person | 200 lux | NR30 – NR35 |
Offices (general, BCO data) | 24°°ä | 22°°ä | 0·25-0·5 ac/h | 8-12 l/s/person | 300-500 lux | NR25 – NR40 |
Retail (shops/stores) | 21-23°°ä | 19-21°°ä | 0·5-1 ac/h | 8 l/s/person | 500-750 lux | NR35 – NR45 |
Swimming pools (pool halls) | 23-26°°ä | 23-26°°ä | 0·5 ac/h | 0-15 l/s/m2 (of wetted area) | 300 lux | NR40 – NR 50 |