Equipment and solar loads | |||
Table 1: Cooling loads | |||
Design area | Application | Other information | Rule of thumb |
Banks | Ìý | Ìý | 160 W/m2 |
Computer suites | Ìý | Ìý | 400 W/m2 approx |
Hotels: | Ìý | Ìý | 150-300 W/m2 |
Offices (general) | Ìý | Ìý | 125 W/m2 |
Ìý | Interior zones more than 7 m from windows | Ìý | 75 W/m2 |
Ìý | Perimeter zones | 60% glazing | 120 W/m2 |
Ìý | up to 6 m | 65% glazing | 180 W/m2 |
Restauarants | Ìý | Ìý | 220 W/m2 |
Retail buildings | Ìý | Ìý | 140 W/m2 |
Table 2: Cooling plant | |||
Design area | Application | Other information | Rule of thumb |
Central cooling plant | Ìý | Load/m2 of floor area | 125 W/m2 |
Ìý | Ìý | Load/m3 of floor volume | 40 W/m3 |
Distributed cooling plant | Ìý | Load/m2 of floor area | 140 W/m2 |
Ìý | Ìý | Load/m3 of floor volume | 45 W/m3 |
Electrical power for refrigeration plant | kW/kW cooling capacity | Central plant | 0·5 kW/kW |
Ìý | Ìý | Distributed plant | 0·78 kW/kW |
Table 3: Solar gains (floor area) | |||
Design area | Application | Other information | Rule of thumb |
Windows with internal blinds | June-September | South facing | 250 W/m2 of glass |
Ìý | June-September | East-West facing | 150 W/m2 of glass |
Clear double glazed with internal blinds | Out of town buildings | All data for 6 m deep, | 2650 W instant |
Ìý | Ìý | 1500 mm wide module. U-value 3·3 W/m2K | 2490 W lag (mass) |
As above with flat slab | Plus brise soleil | Ìý | 1860 W instant |
Ìý | Ìý | Ìý | 1710 lag (mass) |
As above with coffered slab | Plus brise soleil | Ìý | 1860 W instant |
Ìý | Ìý | Ìý | 1680 lag (mass) |
Table 4: Heat loads | |||
Design area | Application | Other information | Rule of thumb |
General buildings | Ìý | Floor area | 90 W/m2 (30 W/m2) |
Educational buildings | Ìý | Ìý | 100 W/m2 |
Industrial buildings | Ìý | Ìý | 80 W/m2 |
Offices | Ìý | Ìý | 70 W/m2 |
Residential buildings | Ìý | Ìý | 60 W/m2 |
Retail buildings | Ìý | Ìý | 110 W/m2 |
Heat gains | Offices | Metabolic | 10 W/m2 |
Ìý | Ìý | Lighting | 12 W/m2 |
Ìý | General offices | Small power loads (diversified over minimum of 1000 m2) | 15 W/m2 |
Electrical systems | |||
Table 1: Electrical supplies and loads | |||
Design area | Application | Other information | Rule of thumb |
Electrical supply | Electrical motors | Above 3 kW rating | 3-phase supply |
Ìý | Electrical motors | Up to and including 3 kW rating | Direct on-line starting |
Ìý | Electrical motors | Above 4 kW rating | Assisted start |
Electrical services load per m2 of building floor area for offices unless otherwise stated | Lighting | Ìý | 10-12 W/m2 |
Ìý | Small power diversified over a minimum of 1000 m2 | Ìý | 15 W/m2 |
Ìý | Air conditioning | Ìý | 60 W/m2 |
Ìý | Passenger lifts | Ìý | 10 W/m2 |
Ìý | Small computer room | Net area | 200-400 W/m2 |
Ìý | Bespoke call centres | Net area | 500-1000 W/m2 |
Total load (kVA) Design allowance for future expansion (percentage) | Total building load | Ìý | Total kW/0·8 |
Ìý | Percentage increase in load | Ìý | Add 25% to exisitng capacity |
Water consumption | |||
Table 1: Hot water demand, daily | |||
Design area | Application | Other information | Rule of thumb |
Dwellings | Single bedroom | Ìý | 115 litres/bedroom |
Ìý | Two bedrooms | Ìý | 75 litres/bedroom |
Ìý | More than three bedrooms | Ìý | 55 litres/bedroom |
Student accommodation, nurses’, children’s and sheltered home | Ìý | Ìý | 70 litres/bedroom |
Care home | Ìý | Ìý | 90 litres/bedroom |
Hotels | Budget | Ìý | 115 litres/bedroom |
Ìý | Four/five star | Ìý | 135 litres/bedroom |
Offices, shops, factories | With canteen | Ìý | 15 litres/person |
Ìý | No canteen | Ìý | 10 litres/person |
Schools | Day school | Ìý | 15 litres/pupil |
Ìý | Boarding school | Ìý | 114 litres/pupil |
Hospitals | District general | Ìý | 200 litres/bed |
Ìý | Surgical and medical wards | Ìý | 110 litres/bed |
Ìý | Paediatric wards | Ìý | 125 litres/bed |
Ìý | Geriatric wards | Ìý | 70 litres/bed |
Sports changing rooms | Sports hall and swimming pool | 20 litres/person | Ìý |
Ìý | Field and all weather pitch | Ìý | 35 litres/person |
Places of assembly | Art gallery, bars and library | Ìý | 2 litres/person (excluding staff) |
Ìý | Museum, theatre, cinema and night club | 1 litre/person (excluding staff) | Ìý |
Table 2: Water demand, daily | |||
Design area | Application | Other information | Rule of thumb |
Dwellings | Single bedroom | Ìý | 210 litres/bedroom |
Ìý | Two bedrooms | Ìý | 130 litres/bedroom |
Ìý | Over three bedrooms | Ìý | 100 litres/bedroom |
Student accommodation | Ìý | Ìý | 90-100 litres/bedroom |
Nurses’ homes and sheltered homes | Ìý | Ìý | 120 litres/bed space |
Children’s home, and elderly care home | Ìý | Ìý | 135 litres/bed space |
Prison | Ìý | Ìý | 150 litres/inmate |
Hotels | Budget | Ìý | 135-150 litres/bedroom |
Ìý | Four/five star | Ìý | 200 litres/bedroom |
Offices, shops, factories | With canteen | Ìý | 45 litres/person |
Ìý | No canteen | Ìý | 40 litres/person |
Schools | Nursery and primary | Ìý | 15 litres/pupil |
Ìý | Secondary | Ìý | 20 litres/pupil |
Ìý | Boarding | Ìý | 90 litres/pupil |
Hospitals | District general | Ìý | 600 litres/bed |
Ìý | Surgical wards | Ìý | 220 litres/bed |
Ìý | Medical wards | Ìý | 220 litres/bed |
Ìý | Paediatric wards | Ìý | 300 litres/bed |
Ìý | Geriatric | Ìý | 140 litres/bed |
Sports changing rooms | Sports hall and swimming pool | 20 litres/person | Ìý |
Field and all weather pitch | Ìý | Ìý | 35 litres/person |
Places of assembly | Art gallery, library and museum | 6 litres/person (excluding staff) | Ìý |
Ìý | Bars and night club | Ìý | 4 litres/person (excluding staff) |